collectd-snmp5
Documentation of collectd's "snmp plugin"
Usage
LoadPlugin snmp# ...<Plugin snmp><Data "powerplus_voltge_input">Table falseType "voltage"TypeInstance "input_line1"Scale 0.1Values "SNMPv2-SMI::enterprises.6050.5.4.1.1.2.1"</Data><Data "hr_users">Table falseType "users"Shift -1Values "HOST-RESOURCES-MIB::hrSystemNumUsers.0"</Data><Data "std_traffic">Table trueType "if_octets"TypeInstanceOID "IF-MIB::ifDescr"#FilterOID "IF-MIB::ifOperStatus"#FilterValues "1", "2"Values "IF-MIB::ifInOctets" "IF-MIB::ifOutOctets"</Data><Data "lancom_stations_total">Type "counter"PluginInstance "stations_total"Table trueCount trueValues "SNMPv2-SMI::enterprises.2356.11.1.3.32.1.10" # SNMPv2-SMI::enterprises.lancom-systems.lcos.lcsStatus.lcsStatusWlan.lcsStatusWlanStationTableTable.lcsStatusWlanStationTableEntry.lcsStatusWlanStationTableEntryState</Data><Data "lancom_stations_connected">Type "counter"PluginInstance "stations_connected"Table trueCount trueValues "SNMPv2-SMI::enterprises.2356.11.1.3.32.1.10" # SNMPv2-SMI::enterprises.lancom-systems.lcos.lcsStatus.lcsStatusWlan.lcsStatusWlanStationTableTable.lcsStatusWlanStationTableEntry.lcsStatusWlanStationTableEntryStateFilterOID "SNMPv2-SMI::enterprises.2356.11.1.3.32.1.10"FilterValues "3" # eConnected</Data><Host "some.switch.mydomain.org">Address "192.168.0.2"Version 1Community "community_string"Collect "std_traffic"Interval 120Timeout 10Retries 1</Host><Host "some.server.mydomain.org">Address "192.168.0.42"Version 2Community "another_string"Collect "std_traffic" "hr_users"</Host><Host "secure.router.mydomain.org">Address "192.168.0.7:165"Version 3SecurityLevel "authPriv"Username "cosmo"AuthProtocol "SHA"AuthPassphrase "setec_astronomy"PrivacyProtocol "AES"PrivacyPassphrase "too_many_secrets"Collect "std_traffic"</Host><Host "some.ups.mydomain.org">Address "tcp:192.168.0.3"Version 1Community "more_communities"Collect "powerplus_voltge_input"Interval 300Timeout 5Retries 5</Host></Plugin>
Overview
The "snmp plugin" queries other hosts using SNMP, the simple network management protocol, and translates the value it receives to collectd's internal format and dispatches them. Depending on the write plugins you have loaded they may be written to disk or submitted to another instance or whatever you configured.
Because querying a host via SNMP may produce a timeout the "complex reads" polling method is used. The ReadThreads parameter in the main configuration influences the number of parallel polling jobs which can be undertaken. If you expect timeouts or some polling to take a long time, you should increase this parameter. Note that other plugins also use the same threads.
Configuration
Since the aim of the "snmp plugin" is to provide a generic interface to SNMP, its configuration is not trivial and may take some time.
Since the "Net-SNMP" library is used you can use all the environment variables that are interpreted by that package. See snmpcmd(1) for more details.
There are two types of blocks that can be contained in the "<Plugin snmp>" block: Data and Host:
The Data block
The Data block defines a list of values or a table of values that are to be queried. The following options can be set:
Typetype-
collectd's type that is to be used, e. g. "if_octets" for interface traffic or "users" for a user count. The types are read from the
TypesDB(see collectd.conf(5)), so you may want to check for which types are defined. See types.db(5) for a description of the format of this file.
Tabletrue|false-
Define if this is a single list of values or a table of values. The difference is the following:
When
Tableis set tofalse, the OIDs given toValues(see below) are queried using the"GET"SNMP command (see snmpget(1)) and transmitted to collectd.Onevalue list is dispatched and, eventually, one file will be written.When
Tableis set totrue, the OIDs given toValues,TypeInstanceOID,PluginInstanceOID,HostOIDandFilterOID(see below) are queried using the"GETNEXT"SNMP command until the subtree is left. After all the lists (think: all columns of the table) have been read, either (Countset tofalse)severalvalue sets will be dispatched and, eventually, several files will be written, or (Countset totrue) one single value will be dispatched. If you configure aType(see above) which needs more than one data source (for example"if_octets"which needs"rx"and"tx") you will need to specify more than one (two, in the example case) OIDs with theValuesoption and can't use theCountoption. This has nothing to do with theTablesetting.For example, if you want to query the number of users on a system, you can use
"HOST-RESOURCES-MIB::hrSystemNumUsers.0". This is one value and belongs to one value list, thereforeTablemust be set tofalse. Please note that, in this case, you have to include the sequence number (zero in this case) in the OID.Counter example: If you want to query the interface table provided by the
"IF-MIB", e. g. the bytes transmitted. There are potentially many interfaces, so you will want to setTabletotrue. Because the"if_octets"type needs two values, received and transmitted bytes, you need to specify two OIDs in theValuessetting, in this case likely"IF-MIB::ifHCInOctets"and"IF-MIB::ifHCOutOctets". But, this is because of theTypesetting, not theTablesetting.Since the semantic of
InstanceandValuesdepends on this setting you need to set it before setting them. Doing vice versa will result in undefined behavior.
PluginPlugin-
Use Plugin as the plugin name of the values that are dispatched. Defaults to
"snmp".
PluginInstanceInstance-
Sets the plugin-instance of the values that are dispatched to Instance value.
When
Tableis set to true andPluginInstanceOIDis set then this option has no effect.Defaults to an empty string.
TypeInstanceInstance-
Sets the type-instance of the values that are dispatched to Instance value.
When
Tableis set to true andTypeInstanceOIDis set then this option has no effect.Defaults to an empty string.
TypeInstanceOIDOID
PluginInstanceOIDOID
HostOIDOID-
If
Tableis set to true, OID is interpreted as an SNMP-prefix that will return a list of values. Those values are then used as the actual type-instance, plugin-instance or host of dispatched metrics. An example would be the"IF-MIB::ifDescr"subtree. variables(5) from the SNMP distribution describes the format of OIDs. When option is set to empty string, then "SUBID" will be used as the value.Prefix may be set for values with use of appropriate
TypeInstancePrefix,PluginInstancePrefixandHostPrefixoptions.When
Tableis set to false orCountis set to true, these options have no effect.Defaults: When no one of these options is configured explicitly,
TypeInstanceOIDdefaults to an empty string.
TypeInstancePrefix
PluginInstancePrefix
HostPrefix-
These options are intented to be used together with
TypeInstanceOID,PluginInstanceOIDandHostOIDrespectively.If set, String is preprended to values received by querying the agent.
When
Tableis set to false orCountis set to true, these options have no effect.The
"UPS-MIB"is an example where you need this setting: It has voltages of the inlets, outlets and the battery of an UPS. However, it doesn't provide a descriptive column for these voltages. In this case having 1, 2, ... as instances is not enough, because the inlet voltages and outlet voltages may both have the subids 1, 2, ... You can use this setting to distinguish between the different voltages.
InstanceInstance-
Attention: this option exists for backwards compatibility only and will be removed in next major release. Please use
TypeInstance/TypeInstanceOIDinstead.The meaning of this setting depends on whether
Tableis set to true or false.If
Tableis set to true, option behaves asTypeInstanceOID. IfTableis set to false, option behaves asTypeInstance.Note what
Tableoption must be set before settingInstance.
InstancePrefixString-
Attention: this option exists for backwards compatibility only and will be removed in next major release. Please use
TypeInstancePrefixinstead.
ValuesOID [OID ...]-
Configures the values to be queried from the SNMP host. The meaning slightly changes with the
Tablesetting. variables(5) from the SNMP distribution describes the format of OIDs.If
Tableis set to true, each OID must be the prefix of all the values to query, e. g."IF-MIB::ifInOctets"for all the counters of incoming traffic. This subtree is walked (using"GETNEXT") until a value from outside the subtree is returned.If
Tableis set to false, each OID must be the OID of exactly one value, e. g."IF-MIB::ifInOctets.3"for the third counter of incoming traffic.
Counttrue|false-
Instead of dispatching one or multiple values per Table entry containing the OID(s) given in the
Valuesoption, just dispatch a single count giving the number of entries that would have been dispatched. This is especially useful when combined with the filtering options (see below) to count the number of entries in a Table matching certain criteria.When
Tableis set to false, this option has no effect.
ScaleValue-
The gauge-values returned by the SNMP-agent are multiplied by Value. This is useful when values are transferred as a fixed point real number. For example, thermometers may transfer
243but actually mean24.3, so you can specify a scale value of0.1to correct this. The default value is, of course,1.0.This value is not applied to counter-values.
ShiftValue-
Value is added to gauge-values returned by the SNMP-agent after they have been multiplied by any
Scalevalue. If, for example, a thermometer returns degrees Kelvin you could specify a shift of273.15here to store values in degrees Celsius. The default value is, of course,0.0.This value is not applied to counter-values.
IgnoreValue [, Value ...]-
The ignore values allows one to ignore TypeInstances based on their name and the patterns specified by the various values you've entered. The match is a glob-type shell matching.
When
Tableis set to false then this option has no effect.
InvertMatchtrue|false(default)-
The invertmatch value should be use in combination of the Ignore option. It changes the behaviour of the Ignore option, from a blacklist behaviour when InvertMatch is set to false, to a whitelist when specified to true.
FilterOIDOID
FilterValuesValue [, Value ...]
FilterIgnoreSelectedtrue|false(default)-
When
Tableis set to true, these options allow to configure filtering based on MIB values.The
FilterOIDdeclares OID to fill table column with values. TheFilterValuesdeclares values list to do match. Whether table row will be collected or ignored depends on theFilterIgnoreSelectedsetting. As with other plugins that use the daemon's ignorelist functionality, a string that starts and ends with a slash is interpreted as a regular expression.If no selection is configured at all,
alltable rows are selected.When
Tableis set to false then these options has no effect.See
Tableand /"IGNORELISTS" for details.
The Host block
The Host block defines which hosts to query, which SNMP community and version to use and which of the defined Data to query.
The argument passed to the Host block is used as the hostname in the data stored by collectd.
AddressIP-Address|Hostname-
Set the address to connect to. Address may include transport specifier and/or port number.
Version1|2|3-
Set the SNMP version to use. When giving
2version"2c"is actually used.
CommunityCommunity-
Pass Community to the host. (Ignored for SNMPv3).
UsernameUsername-
Sets the Username to use for SNMPv3 security.
SecurityLevelauthPriv|authNoPriv|noAuthNoPriv-
Selects the security level for SNMPv3 security.
ContextContext-
Sets the Context for SNMPv3 security.
AuthProtocolMD5|SHA-
Selects the authentication protocol for SNMPv3 security.
AuthPassphrasePassphrase-
Sets the authentication passphrase for SNMPv3 security.
PrivacyProtocolAES|DES-
Selects the privacy (encryption) protocol for SNMPv3 security.
PrivacyPassphrasePassphrase-
Sets the privacy (encryption) passphrase for SNMPv3 security.
CollectData [Data ...]-
Defines which values to collect. Data refers to one of the
Datablock above. Since the config file is read top-down you need to define the data before using it here.
IntervalSeconds-
Collect data from this host every Seconds seconds. This option is meant for devices with not much CPU power, e. g. network equipment such as switches, embedded devices, rack monitoring systems and so on. Since the
Stepof generated RRD files depends on this setting it's wise to select a reasonable value once and never change it.
TimeoutSeconds-
How long to wait for a response. The
"Net-SNMP"library default is 1 second.
RetriesInteger-
The number of times that a query should be retried after the Timeout expires. The
"Net-SNMP"library default is 5.
BulkSizeInteger-
Configures the size of SNMP bulk transfers. The default is 0, which disables bulk transfers altogether.